Voltage Drop Calculator & Guide for Australian Electricians (AS3000 & AS3008 - 2025 Update)
- Casey Doyle
- Jun 17
- 3 min read
Voltage drop is one of the most searched and critical calculations electricians perform daily across Australia.
Getting it wrong can result in non-compliant installations, safety hazards, and costly rework.
In this complete guide, we break down how to calculate voltage drop according to the AS/NZS 3000 (AS3000) and AS/NZS 3008 standards used across Australia.
We also cover the best tools, formulas, and common mistakes electricians need to know.
Whether you're a licensed electrician, apprentice, or business owner. This guide is designed to help you stay compliant and efficient.
What is Voltage Drop?
Voltage drop is the reduction in voltage that occurs when current flows through cables and conductors due to electrical resistance.
The longer the cable run or the higher the load, the greater the voltage drop. If voltage drop exceeds allowable limits, electrical equipment may not function correctly, and the installation may fail compliance checks.
AS3000 Rules for Voltage Drop in Australia
The AS/NZS 3000 (Wiring Rules) is the national standard governing all electrical installations in Australia.
The rule for voltage drop is clear:
The voltage drop from the point of supply to any equipment or outlet must not exceed 5 percent of the nominal supply voltage.
For most common Australian installations:
Single-phase (230V): Maximum voltage drop = 11.5V
Three-phase (400V): Maximum voltage drop = 20V
This limit applies to the total voltage drop across all wiring runs. Including mains, submains, and final subcircuits.
Factors That Affect Voltage Drop
To calculate voltage drop accurately under AS3000, you need to account for:
Total cable length (both active and neutral for single-phase circuits)
Load current (Amps)
Cable size (mm²)
Conductor material (Copper or Aluminium)
Installation conditions (temperature, grouping, insulation)
Power factor (especially for larger loads)
Voltage Drop Formula (Simplified)

Where:
Vd = Voltage drop (Volts)
L = Length of cable run (metres)
I = Current (Amps)
Vc = Voltage drop per amp per metre (from AS3008 tables)
The AS3008 standard provides detailed tables of voltage drop values for each cable type and installation condition.
Example Calculation (Single Phase Example)

Scenario:
230V single-phase
Load: 20A
Cable length: 50m
Copper cable: 6mm²
Voltage drop per amp per metre: 7.3 mV/A/m (from AS3008)
Result: Voltage drop is 14.6V, which exceeds the allowable 11.5V limit. This circuit would be non-compliant. A larger cable size would be required.
Tools and Resources to Calculate Voltage Drop
While manual calculations are useful for understanding the fundamentals, most electricians use voltage drop calculators to speed up compliance on site, especially when working under Australian standards.
There are several voltage drop calculators commonly used by electricians in Australia, including:
jCalc.net
ElecCalc Pro / Cable Pro
Electrical Calculators Australia (various apps and online tools)
AS3008-based spreadsheets
However, many of these calculators are either designed overseas, use slightly different formulas, or are not fully aligned with AS3000 and AS3008 Australian standards. This can create confusion or errors when electricians are trying to stay compliant.
That’s why Sparki Connect is being built. A fully Australian-compliant tool designed for real-world use on Australian job sites, following AS3000 and AS3008 exactly.
Common Mistakes Electricians Make With Voltage Drop
Not including the full length of both active and neutral runs
Ignoring ambient temperature and grouping correction factors
Using incorrect tables or data from non-Australian standards
Forgetting to include submains and final subcircuits together
Using apps or calculators not based on AS3008 data
How Sparki Connect Is Building A Fully Compliant Australian Calculator
At Sparki Connect, we are developing a fully AS3000 and AS3008 compliant calculator system purpose built for Australian electricians. Unlike many overseas tools, Sparki Connect is:
Fully aligned with AS3008 tables
Includes Australian correction factors
Built for real world use on site
Designed by electricians, for electricians
When released, Sparki Connect’s voltage drop calculator will simplify compliance, reduce risk, and save electricians time on every job.
Conclusion
Voltage drop calculations are one of the most critical compliance requirements under AS3000 for every Australian electrician.
Understanding how to calculate and check voltage drop properly ensures safe, reliable installations and protects your license.
Bookmark this guide, reference the formulas, and always double check your calculations using AS3008 data.
With new tools like Sparki Connect emerging, Australian electricians will soon have better local options to simplify compliance even further.
Comments